UNITRONIC® BUS PB FD FRNC FC
Highly flexible application
Bus cables can be used for PROFIBUS-DP, -FMS as well as FIP. UL/CSA certified, halogen-free, flame-retardant, oil-resistant. Temp. range from -40°C to +80°C
Benefits
- Fast Connect (FC) system
- For use wherever the combination of a halogen-free outer sheath with properties similar to polyurethane and enhanced flame-retardance is required
- For highly flexible applications (drag chains, frequently moving machine components)
- Cables can be used for PROFIBUS-DP as well as PROFIBUS-FMS and FIP
Application range
- For highly flexible use in power chains, permanently moving machines and linear robots
- This cable provides special advantages in sensitive areas where fire propagation must be avoided and the presence of toxic fumes in the event of a fire would cause personal injury and damage to equipment.
Product features
- The cable is UL/CSA-certified (CMG)
- Halogen-free
- Highly flame-retardant in accordance with IEC 60332-3 and FT4
- Oil-resistant
- Based on the bit rates listed, in accordance with PNO specifications the following maximum cable lengths for a bus segment apply
(cable type A, PROFIBUS-DP):
93.75 kbit/s = 1200 m
187.5 kbit/s = 1000 m
500 kbit/s = 400 m
1.5 Mbit/s = 200 m
12.0 Mbit/s = 100 m
Design
- Stranded bare copper wire
- Foam Skin – core insulation (O2YS)
- Overall shielding with copper braiding and plastic-laminated aluminium foil
- Screening braid made of tin-plated copper wires
- Outer sheath: Polyurethane (PUR) compound
Classification
- ETIM 5.0 Class-ID: EC000830
- ETIM 5.0 Class-Description: Data cable
Operating capacitance
- nom. 28 nF/km
Peak operating voltage
- (not for power applications)
250 V
Minimum bending radius
- Fixed installation: 10 x outer diameter
- Flexing: 15 x outer diameter
Test voltage
- Core/Core: 1500 V eff.
Characteristic impedance
- (3 – 20 MHz): 150 ±15 ohm
Temperature range
- Flexing: -30°C to +70°C
- Fixed installation: -40°C to +80°C
Article number | Article designation | Number of pairs and conductor diameter (mm) |
Outer diameter (mm) | Copper index (kg/km) | Weight (kg/km) |
2170854 | UNITRONIC®BUS PB FD FRNC FC | 1x2x0.64 | 8 | 26 | 75 |