Download : 301-FRS015-B01P-3M05
SHIELDED/UNSHIELDED FIRE RESISTANT CONTROL CABLE
Description
Alantek Fire Resistant Control Cable consists of Bare Copper Conductor
with Mica Tape, XLPE Insulation , with or without Aluminium Foil and
Outer LSZH Jacket
Application
Multipair Control Cable for industrial, alarm, PA and critical system.
Tested in accordance to IEC 60332-3A, IEC 60331, BS 5308 or/and BS
6387 CZW
Colour Code
• 1 pair : Black, White
• > 1 pair : Black, White with numberings (1, 2, 3, 4, cont.)
Cable Properties
Cable Counts | Conductor Stranded annealed Copper | Mica Tape | Insulation XLPE |
Shield | Drain Wire | Jacket LSZH (Orange colour) | |
mm2 | No./mm | Thickness (mm) |
Laminated Aluminium polyester tape | Tinned strand copper wire No./mm | OD (mm) ±0.6 |
||
Unshielded, 1-pair | 1.5 | 7/0.53 | 2 layer | 0.60 | Nil | Nil | 8.3 |
Unshielded, 1-pair | 2.5 | 7/0.67 | 2 layer | 0.70 | Nil | Nil | 9.5 |
Unshielded, 2-pair | 1.5 | 7/0.53 | 2 layer | 0.60 | Nil | Nil | 12.8 |
Unshielded, 2-pair | 2.5 | 7/0.67 | 2 layer | 0.70 | Nil | Nil | 14.7 |
Shielded, 1pair | 1.5 | 7/0.53 | 2 layer | 0.60 | Yes | 16/0.2mm | 8.5 |
Shielded, 1pair | 2.5 | 7/0.67 | 2 layer | 0.70 | Yes | 16/0.2mm | 9.7 |
Shielded, 2pair | 1.5 | 7/0.53 | 2 layer | 0.60 | Yes | 16/0.2mm | 13.0 |
Shielded, 2pair | 2.5 | 7/0.67 | 2 layer | 0.70 | Yes | 16/0.2mm | 14.9 |
Unshielded, 1-pair | 1.5 | 7/0.53 | 2 layer | 0.60 | Nil | Nil | 9.3 |
Unshielded, 1-pair | 2.5 | 7/0.67 | 2 layer | 0.70 | Nil | Nil | 10.5 |
Unshielded, 2-pair | 1.5 | 7/0.53 | 2 layer | 0.60 | Nil | Nil | 14.4 |
Unshielded, 2-pair | 2.5 | 7/0.67 | 2 layer | 0.70 | Nil | Nil | 16.4 |
Shielded, 1pair | 1.5 | 7/0.53 | 2 layer | 0.60 | Yes | 16/0.2mm | 9.5 |
Shielded, 1pair | 2.5 | 7/0.67 | 2 layer | 0.70 | Yes | 16/0.2mm | 10.7 |
Shielded, 2pair | 1.5 | 7/0.53 | 2 layer | 0.60 | Yes | 16/0.2mm | 14.6 |
Shielded, 2pair | 2.5 | 7/0.67 | 2 layer | 0.70 | Yes | 16/0.2mm | 16.6 |
ShIELDED/UNShIELDED FIRE RESISTANT CONTROL CABLE | |||
STT | Part number | Mô Tả | |
1 | 301-FRU015-E05P-3M05 | 5PR X1.5MM2 FIRE RESISTANT UNSHIELDED CABLE ORANGE IEC 60331 | rl (500m) |
2 | 301-FRS015-E05P-3M05 | 5PR X 1.5MM2 FIRE RESISTANT SHIELDED CABLE ORANGE IEC 60331 | rl (500m) |
3 | 301-FRU015-B01P-3M05 | Alantek 1Pair X 1.5MM2 FR Unshielded Cable, Orange IEC 60331 & BS 6387 C W Z | rl (500m) |
4 | 301-FRU025-B01P-3M05 | Alantek 1Pair X 2.5MM2 FR Unshielded Cable, Orange IEC 60331 & BS 6387 C W Z | rl (500m) |
5 | 301-FRS015-B01P-3M05 | Alantek 1Pair X 1.5MM2 FR Shielded Cable, Orange IEC 60331 & BS 6387 C W Z | rl (500m) |
6 | 301-FRS025-B01P-3M05 | Alantek 1Pair X 2.5MM2 FR Shielded Cable, Orange IEC 60331 & BS 6387 C W Z | rl (500m) |
7 | 301-FRS015-E01P-3M05 | 1-pair 1.5MM2 Fire Resistant Shielded Cable, IEC 60331, Orange | rl (500m) |
8 | 301-FRS025-E01P-3M05 | 1-pair 2.5MM2 Fire Resistant Shielded Cable, IEC 60331, Orange | rl (500m) |
9 | 301-FRS015-E02P-3M05 | 2-pair 1.5MM2 Fire Resistant Shielded Cable, IEC 60331, Orange | rl (500m) |
10 | 301-FRS025-E02P-3M05 | 2-pair 2.5MM2 Fire Resistant Shielded Cable, IEC 60331, Orange | rl (500m) |
11 | 301-FRS015-B02P-3M05 | 2-pair 1.5MM2 Fire Resistant Shielded Cable, BS 6387 CWZ, Orange | rl (500m) |
12 | 301-FRS025-B02P-3M05 | 2-pair 2.5MM2 Fire Resistant Shielded Cable, BS 6387 CWZ, Orange | rl (500m) |